12.9.1 Arms Storage

New Facility Criteria (AR 190-11 was revised on 15 Nov 2006).

If Category II arms are to be stored in new facilities built for the principal purpose of storing arms, the facilities will meet the following facility criteria. 

12.9.1.1 Walls

Walls will be of 8 inches of concrete reinforced with No. 4 reinforcing bars at 9 inches on center in each direction in each face of the wall. Reinforcement in the 2 faces of the wall will be staggered on each face to form a projected grid approximately 4–1/2 inches square. Reinforcement in the walls will be tied into floors and ceilings in accordance with American Concrete Institute standards.

12.9.1.2 Ceilings and Roofs

Ceilings and roofs will be of reinforced concrete construction. The thinnest portion may not be less than 6 inches. reinforcing bar spacing will form a grid so that the area of any opening does not exceed 96 square inches using No. 4 bars or larger.

12.9.1.3 Floors

Floors, if on grade, will be a minimum of 6–inch thick reinforced concrete construction reinforced with 6 inches by 6 inches, W4 by W4 welded wire fabric or equivalent steel reinforcing bars (based on area of steel per square foot). Where the floor slab acts as the ceiling of an underlying room or area, the ceiling standards will apply. Where equivalent steel reinforcing bars are used, bar spacing will form a grid so that the area of any opening does not exceed 96 square inches.

12.9.1.4 Door and door frames

The door will be GSA approved Class 5 armory door per GSA Fed Spec AA–D–600D. A GSA approved Class 5 vault door is not encouraged due to its electromechanical lock. Double door protection for arms storage facilities is not required. Door frames will be per Fed Spec AA–D–600D

12.9.1.5 Windows and other Openings

Windows are not authorized. Ducts, vents, and other openings of 96 square inches or more with the least dimension greater than 6 inches will be secured in accordance with 1 of the following methods and otherwise limited to the minimum number and size that are essential

  • Sealed with material comparable to that forming the adjacent walls.

  • fitted with any of the barriers below with bars or steel mesh securely embedded in the structure of the building or welded to a steel frame that will be securely attached to the wall with fastenings inaccessible from the exterior of arms storage facility.

    • Three–eighth inch or larger hardened steel bars with vertical bars not more than 4 inches apart and with horizontal bars welded to the vertical bars so that the openings do not exceed 32 square inches.

    • A minimum of 8–gauge high carbon manganese steel mesh with 2–inch diamond grid.

    • A 6–gauge cold drawn steel wire mesh with 2–inch diamond grid when 8–gauge mesh above is not available.

 

 
 

Area Specifications